Economy series vs Standard Type Q Setting Parameter Description
Saving
Press and hold the MODE key and the left shift key at the same time until Cod ( ) is displayed,
up to
and in this state, enter and modify the state of Cod ( ) = 0020 through and keys.
Temperature Controllers 68 % Symbol Code Meaning Other Description Range Default
Display
Value
Select
Relay output / SSR drive output free switching SN sensor Different input models K, J, R, S, B, E, N, T, PT, K
Cu, O.K, 0-50, 0-5V, 1-50
input signal need to match different input resistors.
Easy connection to PLC
with RS485 communication function Unit Unit
selection °C: Celsius degree; °F: Fahrenheit degree °C, °F °C
Can be installed in the control cabinet for use
OUT Output RLY: Switch relay output RLY RLY
Method SSR: DC12V output
Adopting terminal block wiring structure
HOT: Heating control, i.e. reverse control;
COL: Cooling control, i.e. forward control;
H-C: Simultaneous control of heating and cooling HOT, COL, H-C
Control Note: For COL and H-C
Dir Direction The output control of both HOT and COL modes is OUT1 control modes, only HOT
22 Q External Dimension and Opening Dimension Q Function Description of Control Panel H-C mode OUT1 is heating control output RLY mode is applicable.
OUT2 is cooling control output
Name of Each Part
Heaters / Temperature Sensors / Heat Insulating Plates (with RS485 communication) 1 1 Current Value (PV) Display (Red) Tt temperatures the set value within the range of the set value ±Tt 0-10 6
C-MTCTRS
C-MTCTRST
Number of
Make the display temperature close to
The current measured value (PV)
is displayed in the operation mode,
tracked
and the internal parameter name is
0: Manual control prohibited;
displayed in the setup mode.
4
Whether
2 Setting Value (SV) Display (Green)
1: Manual control allowed
3
manual
8
target (SV) is displayed in the
used to enter and exit the manual control state, and or
7
operation mode, and the current
allowed
key can be used to control the output power percentage
5 2 The setting value of the control Hnd control is When the manual control is allowed, the shift key can be 0, 1 0
setting value of that parameter is
Display
Cartridge Heaters COM/ F 3 Control/Alarm Output Indicator displayed in the setup mode. Over 0-Turn off the function
of the instrument in the manual control state.
6
Other value, when exceeding the setting value.
- When performing self-tuning, the AT light flashes in a cycle of 1 second.
* When SSR controls the cycle/phase control of the drive output mode, the FAC temperature The excess part is displayed in proportion, with the 0-100 0
display limit
light is on when the operation amount exceeds 3.0%.
P.1529 - AL1/AL2: The light is on when Alarm1 and Alarm2 alarm output is ON. displayed value = SV+(PV-SV)/FAC
Temperature Sensors External 48mm×48mm 48mm×96mm 5 Key: Used to enter the parameter group setting, return to the COD = 0040 Access to factory parameters 4
4 OUT: The light is on when the control output (Main Control Output) is ON.
operation mode, switch the parameter group, and save the setting value.
Size
6 Direction Key: Used to enter the setting value change mode or move the
1 CTON = 1000 Allowed to directly modify the SU value through the plus or minus key, and SU is not displayed in the upper row
digit to change the value up/down.
= 0001 With CT function
L × W × H
P.1537 Housing Size 45mm×45mm×75mm 45mm×92mm×75mm 7 Function Key: Pressing key and key simultaneously for 3 seconds 2 TON = 0000 Alarm 1 is an excitation alarm
will activate the [DI-K] digital input key function (run/stop, alarm clear,
0001 Alarm 1 is an non-excitation alarm
Mounting
self-tuning) setting.
Temperature Controllers Q Comparison with generic products in the market = 0000 Alarm 2 is an excitation alarm
45mm×45mm
45mm×92mm
Size
8 Temperature Unit Indicator (°C/°F) : Displays the current temperature unit.
0010 Alarm 2 is an non-excitation alarm
= 1000 With ET timing function
Tap the shift key to turn on the output
P.1551 Comparison of anti-disturbance performance First overshoot comparison 3 CON = 0001 Allowed to manually turn on and turn off the output, and enter the closed output state when powered on
0100 With the communication function
Heat Insulation Plates *Generic products on the market MISUMI Economy series products *Generic products on the market MISUMI Economy series products COD = 0060 Access to factory parameters 5
1000 Allowed to turn on the adaptive function
Small hunting and short time to reach and
MISUMI Economy series
Large hunting and long time to reach and
Traditional PID control
intelligent PID control
stabilize the set temperature
stabilize the set temperature
P.1555 +3 Temperature +3 Temperature t2 1 LBAT Output fault monitoring time
2 LBAB Output fault monitoring width
t1
Temperature Temperature LBAT Heating output monitoring time, in seconds.
Time Time LBAB Heating output monitoring width, in the same unit as PV value.
-3 -3 A heating fault is indicated when the PV measured temperature change is less than LBAB
after a full-cycle heating output or a full-cycle shutdown output with a duration of LBAT time, and no heating fault is indicated
Temperature Temperature
Set Temperature Set Temperature if the change is greater than LBAB.
SV=EER1 Indicate heating failure.
Current Temperature Current Temperature 3 RLRS Solid state and relay selection output
Time Time SrrL Select whether the heating type is relay or solid-state signal output
Set Temperature Set Temperature
Generic products on the market MISUMI Economy series =0 Relay heating =1 Solid-state heating
Current Temperature Current Temperature temperature control instrument
Time Time
COD=1168 Restore factory settings